What is IFGC Gas Sizing for Standby Power Systems?
Mathematical Foundation
Laws & Principles
- The IFGC Longest Run Method: When sizing the branch line specifically for the generator, you must use the total length of the pipe from the meter to the generator. You DO NOT reset the distance measurement at tees.
- Pressure Drop Constraints: Standard residential natural gas systems operate at low pressure (7-11 inches water column). Generator manufacturer sizing charts are strictly based on allowing no more than a 0.5-inch to 1-inch w.c. pressure drop across the entire pipe run. Exceeding this drop guarantees starting failures.
- BTUH Equivalencies: 1 Cubic Foot per Hour (CFH) of Natural Gas equals approximately 1,000 BTUH. 1 CFH of Propane equals approximately 2,500 BTUH. Because propane has more than double the energy density, a smaller diameter pipe can carry the same equivalent kilowatt capacity as a larger natural gas pipe.
- Dedicated Runs: Best practice explicitly dictates running a dedicated, unbroken line from the meter directly to the generator. Tapping into an existing 3/4-inch branch line that also feeds a furnace and a water heater is the #1 cause of generator installation failures.
Step-by-Step Example Walkthrough
" A homeowner installs a 22kW standby generator. The manufacturer specifies a full-load demand of 281,000 BTUH of Natural Gas. The generator is located 72 pipe-feet away from the gas meter. "
- 1. Identify the fuel and load: Natural Gas at 281k BTUH.
- 2. Identify the length: 72 feet. Because charts jump in specific increments, we must slide UP to the next longest tier: 100 feet.
- 3. Look at the 100-foot Natural Gas row on the IFGC table.
- 4. Check 1-inch pipe capacity at 100 ft: It can carry 195,000 BTUH. (FAIL — Too small for 281k).
- 5. Check 1-1/4 inch pipe capacity at 100 ft: It can carry 400,000 BTUH. (PASS — Satisfies 281k).