What is Motor Capacitor Sizing (Microfarads)?
Mathematical Foundation
Laws & Principles
- Never replace a capacitor with one of lower voltage rating. A 440V cap can replace a 370V cap, but not vice versa.
- Most HVAC run capacitors have a ±6% tolerance. If the measured microfarads fall below this, it must be replaced.
- Always discharge a capacitor safely by shorting its terminals with an insulated tool before measuring.
- Start capacitors are typically black plastic and high microfarad (100+ μF). Run capacitors are silver metal and low microfarad (5 to 80 μF).
Step-by-Step Example Walkthrough
" Testing an AC condenser motor capacitor under load to verify its health. "
- 1. Warning: Motor must be running for this test.
- 2. Measure Amps: Clamp meter on the start wire (usually brown) reads 3.2 Amps.
- 3. Measure Volts: Multimeter across the capacitor terminals reads 325 Volts.
- 4. Calc Rule of Thumb: (3.2 * 2652) / 325 = 8486.4 / 325.
- 5. Result: 26.1 μF.