What is 3-Phase Voltage Drop Engineering?
Mathematical Foundation
Laws & Principles
- NEC 210.19(A) Information Note: A voltage drop exceeding 3% at the farthest outlet leads to inefficient operation.
- The 1.732 multiplier accounts for the 120-degree phase shift in 3-phase power (sqrt(3)).
- Resistance (R) should be based on uncoated copper at 75°C for standard calculations.
- Voltage at Load = System Voltage - Calculated Drop.
- UPSIZE conductors if the percentage drop exceeds the equipment's tolerance (typically 3-5%).
Step-by-Step Example Walkthrough
" 480V, 100A load at 500ft using 2 AWG Copper. "
- 1. Find Resistance: 2 AWG = 0.16 Ohms per 1000ft.
- 2. Apply 3-Phase Formula: (1.732 * 500 * 0.16 * 100) / 1000.
- 3. Calculation: 13,856 / 1000 = 13.86 Volts Drop.
- 4. Percentage: (13.86 / 480) * 100 = 2.89%.