What is Physics of Line Resistance (NEC 210.19)?
Mathematical Foundation
Laws & Principles
- The 3% Branch Rule: NEC Section 210.19(A) Informational Note 4 strictly recommends a maximum voltage drop of 3% for the final branch circuit feeding the machine. Dropping past this voids manufacturers warranties.
- The 5% Feeder Rule: The total system drop (the feeder from the pole to the main panel + the branch from the panel to the plug) must not collectively exceed 5%.
- Linear Failure: Distance is the ultimate enemy. The relationship is perfectly linear. If 100 feet of wire drops 2%, then 200 feet drops 4% (Failing NEC). To fix this, you must buy physically thicker wire.
- Copper vs. Aluminum: Aluminum is a terrible conductor compared to copper. Over long distances, you typically must jump up two full wire sizes (e.g., from 4/0 Copper to 300 KCMIL Aluminum) just to survive the voltage drop.
Step-by-Step Example Walkthrough
" Wiring a 15-amp load on a 120V single-phase circuit using standard 12 AWG Copper wire, running 125 feet out to a detached shed. "
- 1. Identify K-Factor: Copper = 12.9.
- 2. Identify CM for 12 AWG: 6,530 Circular Mils.
- 3. Apply single-phase formula: (2 × 12.9 × 15 Amps × 125 feet run) / 6,530 CM.
- 4. Calculate Raw Drop: 48,375 / 6,530 = 7.4 Volts dropped along the wire.
- 5. Calculate Percentage: (7.4V Drop / 120V Source) × 100 = 6.1% Drop.