What is Load-Based Cooling Tower Water Accounting?
Mathematical Foundation
Laws & Principles
- THE RULE OF THIRDS (AT 1.5 CYCLES): If a tower operates at an incredibly poor 1.5 Cycles of Concentration, the equation dictates that Blowdown = Evaporation / 0.5. At this terrible setting, the tower is literally dumping TWICE as much water down the drain as it is evaporating. This will bankrupt the owner via water utility bills.
- THE LAW OF DIMINISHING RETURNS: Moving a chemical treatment program from 2.0 Cycles to 4.0 Cycles cuts the blowdown drain by 66%. However, moving from 6.0 Cycles to 8.0 Cycles provides almost zero mathematical water savings while massively spiking the risk of petrifying the chiller tubes with calcium scale.
- THE MAKEUP VALVE CRITICALITY: During peak summer load, the municipal makeup valve must physically provide M (Total Makeup) continuously. If the civil engineer sizes the makeup line for the 'average' annual load instead of the peak summer load, the float valve will fail to keep up, the basin will run completely dry, and the vortexing air will cavitate and destroy the massive condenser pumps.
Step-by-Step Example Walkthrough
" During the construction design phase, an MEP engineer must size the makeup water pipe for a new 1,200-Ton centrifugal chiller plant. The local water treatment specialist indicates they can safely hold 4.0 Cycles of Concentration. "
- 1. Calculate Peak Evaporation: E = 1,200 Tons × 0.03 = 36.0 GPM of pure vapor.
- 2. Calculate forced Blowdown: B = 36.0 GPM / (4.0 - 1) = 36.0 / 3 = 12.0 GPM into the sewer.
- 3. Calculate Total grid Makeup obligation: 36.0 GPM + 12.0 GPM = 48.0 GPM.