What is The Physics of PumpAffinity?
Mathematical Foundation
Laws & Principles
- The Pump Affinity Laws dictate that shaft horsepower demand mathematically scales by the cube of the impeller speed. Reducing pump RPM by exactly half physically requires only 1/8th (12.5%) of the original motor horsepower.
- The laws strictly assume geometrically similar pump casings and absolute constant system efficiency, meaning extreme low-speed calculations may analytically underpredict actual VFD parasitic losses.
Step-by-Step Example Walkthrough
" A 10 HP chilled water booster pump delivering 400 GPM at 1,750 RPM is throttled down by a Variable Frequency Drive to 1,400 RPM to save facility energy. "
- 1. Calculate the speed reduction ratio (N2 / N1) = 1,400 / 1,750 = 0.80 (80%).
- 2. Flow capacity (Q) drops linearly: 400 GPM * 0.80 = 320 GPM.
- 3. Brake Horsepower drops by the cube (0.80³ = 0.512 multiplier): 10 HP * 0.512 = 5.12 BHP.