Calcady
Home / Trade / Renewable / Battery Capacity Sizer

Battery Capacity Sizer

Determine the total raw battery capacity in Amp-Hours needed to survive off-grid cloudy days, adjusting for strict chemistry safe discharge limits.

Storage Load Paramters

Watt-hours (Wh)
days

Consecutive cloudy days

Lithium batteries can safely be drained much lower than Lead-Acid batteries before suffering permanent chemical damage.

Required Battery Block

Required Rating

625

Amp-HoursAh

Total Gross

30.0

kWh
Pure Usable Energy Need15,000 Wh
Total Gross Battery Capacity30,000 Wh

Depth of Discharge Penalty: Because Lead-Acid batteries shouldn't be discharged below 50% of their total capacity, you must physically purchase double your required usable energy.

Email LinkText/SMSWhatsApp

Quick Answer: How many Amp-Hours of batteries do I need for off-grid solar?

The formula: Gross Bank Capacity (Ah) = (Daily Load × Days of Autonomy) ÷ DoD ÷ System Voltage. For a typical off-grid cabin running 5 kWh/day with 3 days of autonomy on a 48V LiFePO4 system at 80% DoD: (5,000 × 3) ÷ 0.80 ÷ 48 = 391 Ah. The same load on lead-acid at 50% DoD requires 625 Ah — 60% more physical battery. The Depth of Discharge limit is not optional: discharging lead-acid below 50% permanently sulfates the plates; discharging LiFePO4 below 20% accelerates lithium plating and dendrite formation. This calculator applies the correct DoD limit for each chemistry automatically.

Battery Chemistry Comparison for Off-Grid Solar

Chemistry Max DoD Cycle Life Upfront Cost/kWh Best For
Flooded Lead-Acid (FLA) 50% 200–400 cycles $100–$150 Budget off-grid; seasonal cabins; low-cycle applications; easily serviced/refilled
AGM (Sealed Lead-Acid) 50% 300–500 cycles $150–$250 Maintenance-free; RVs; cold climates (better cold performance than FLA); UPS backup
Gel Cell 50–60% 500–800 cycles $200–$300 Slow discharge applications; telecom; stationary backup; sensitive to overcharging
LiFePO4 (Lithium Iron Phosphate) 80% 2,000–4,000 cycles $400–$700 Preferred for residential off-grid; lightweight; flat discharge curve; built-in BMS; 10+ year life
NMC Lithium (Li-Ion) 80–90% 500–1,500 cycles $300–$500 Higher energy density than LiFePO4; EV-grade repurposed cells; requires careful BMS management; thermal runaway risk if abused
Cost per cycle = (Upfront cost/kWh) ÷ Cycle life. LiFePO4 at $600/kWh ÷ 3,000 cycles = $0.20/kWh-cycle vs. FLA at $125/kWh ÷ 300 cycles = $0.42/kWh-cycle — LiFePO4 is 53% cheaper per cycle despite 4–5× higher upfront cost. Always compare cost-per-cycle, not sticker price.

Pro Tips & Battery Bank Sizing Errors

Do This

  • Use a 48V system for any bank above 5 kWh — higher voltage dramatically reduces wire gauge, fusing, and heat losses. Power (W) = Voltage × Current. For the same 5 kW of load: at 12V, current = 417A (requires 4/0 AWG cable, expensive fusing); at 48V, current = 104A (requires 4 AWG cable, standard 150A fuse). Wire resistance loss = I²R — reducing current by 4× reduces loss by 16× for the same wire run. All modern inverter/chargers (Victron, Schneider, SMA) support 48V natively. Below 3 kWh, 12V or 24V systems are still practical. Never mix 12V and 24V batteries in the same bank.
  • Derate lead-acid battery capacity by 20–30% for cold-weather installations — a 100 Ah battery at 32°F (0°C) delivers only 70–80 Ah. Lead-acid battery capacity decreases approximately 1% per °F below 77°F (25°C), reaching about 50% capacity at 0°F (−18°C). If your battery bank is in an unheated space (garage, shed) in a cold climate, add a temperature correction factor: multiply your calculated bank size by 1.2–1.4 for winter conditions. LiFePO4 batteries also lose capacity in cold (−20% at 32°F), but they recover fully when warmed — unlike lead-acid, which permanently loses capacity from repeated cold-discharge cycling. Install insulation or a battery heater (2–5W trickle) for cold installations.

Avoid This

  • Don't mix batteries of different ages, chemistries, or capacities in the same parallel bank. When batteries are connected in parallel, the stronger (newer/fuller) battery always forces current into the weaker one, causing the weaker cell to charge faster than designed, generating heat, and accelerating degradation. The “birthday problem” in battery banks: a single weak cell tanks the entire parallel group's available capacity because current redistribution creates uneven state-of-charge across cells. If replacing cells in an existing lead-acid bank, replace the entire bank at once. For LiFePO4, individual cells with matched capacity can be added if within ±5% of existing SoC at the time of connection.
  • Don't confuse C-rate when purchasing: a battery rated “100 Ah” is usually rated at the C20 rate (20-hour discharge) — at C5 (5-hour discharge), it may only deliver 75–85 Ah. Lead-acid batteries lose effective capacity significantly at high discharge rates. Peukert's Law: Cactual = Crated × (t/T)1−k, where k ≈ 1.1–1.3 for FLA. An inverter drawing 500W from a 100Ah/12V bank (C2.4 rate) effectively delivers only ~75Ah, not 100Ah. For inverter applications (high discharge rate), size for the C5 or actual discharge rate capacity, not the C20 spec sheet number. This calculator uses the rated capacity — always verify the C-rate your load requires against the manufacturer's rate-dependent capacity chart.

Frequently Asked Questions

How many days of autonomy should I design for?

Standard design rules by application: Off-grid residential: 3 days (weathers most storm systems; beyond 3 days, a generator is more cost-effective than additional battery capacity). Grid-tied with battery backup: 0.5–1 day (covers typical grid outages; longer outages suggest generator pairing). RV/boat: 1–2 days (frequent partial recharge from alternator, shore power, or generator). Critical infrastructure (telecom, medical): 5–14 days (mandated by regulatory standards). Beyond 5 days of pure battery autonomy, the cost and weight of additional batteries typically exceeds the cost of a propane or diesel generator for bridging long outages. The NEC Article 706 (storage systems) and UL 9540 govern residential energy storage installation requirements in most US jurisdictions.

Should I wire batteries in series or parallel?

Series wiring adds voltages while keeping Ah constant: two 12V/100Ah batteries in series = 24V/100Ah (2,400 Wh). Parallel wiring adds Ah while keeping voltage constant: two 12V/100Ah batteries in parallel = 12V/200Ah (2,400 Wh — same Wh). To build a 48V bank from 12V batteries, wire 4 batteries in series (4 × 12V = 48V). To double the capacity of that 48V bank, wire a second group of 4 in parallel with the first. The result: 48V at twice the Ah. Series-parallel rule: always use identical batteries (same brand, model, age, and SoC at connection time). For large banks, many solar designers prefer 48V batteries (marketed as single units) over series-wired 12V strings to minimize cell imbalance risk. Modern LiFePO4 packs with built-in BMS automatically handle cell balancing in series configurations.

Is LiFePO4 worth the higher upfront cost over lead-acid?

In most daily-cycle off-grid applications, yes — LiFePO4 is cheaper over its lifetime despite 3–5× higher purchase price. Cost-per-cycle analysis (see chemistry table above): LiFePO4 at ~$600/kWh ÷ 3,000 cycles ≈ $0.20/kWh-cycle; flooded lead-acid at ~$125/kWh ÷ 300 cycles ≈ $0.42/kWh-cycle. LiFePO4 wins by 53% per cycle and eliminates: monthly equalization charges, water refilling, hydrogen off-gassing ventilation requirements, temperature sensitivity, and the 2× bank oversizing penalty of lead-acid. Lead-acid remains justified for: seasonal cabins cycling <30 times per year (cycle count too low to matter), budget-constrained projects where upfront cost is the primary constraint, or cold-storage applications where LiFePO4 BMS low-temperature cutoff is a constraint.

How do I calculate my daily load in Watt-hours?

Daily load (Wh) = sum of (appliance watts × hours per day) for all loads. Practical steps: (1) List every electrical device and its wattage (check the label or use a kill-a-watt meter for measured consumption). (2) Estimate daily usage hours. (3) Multiply and sum: e.g., LED lights 50W × 5h = 250 Wh; refrigerator 150W average × 24h = 3,600 Wh; laptop 45W × 4h = 180 Wh. Sum = 4,030 Wh/day. (4) Add inverter efficiency loss: divide by inverter efficiency (typically 85–95%) to get DC load: 4,030 ÷ 0.90 ≈ 4,478 Wh/day AC equivalent at the battery. (5) Add safety factor of 10–20% for startup surges, measurement errors, and future load growth. A realistic off-grid cabin typically runs 3–8 kWh/day depending on whether it has a standard refrigerator, electric water heater (very high load — solar thermal is far more efficient), or resistance space heating (avoid on off-grid — use a propane heater instead).

Related Calculators