What is Grounding Electrode Conductor Sizing?
Mathematical Foundation
Laws & Principles
- NEC 2023 Table 250.66 sets the minimum GEC size from the largest ungrounded service-entrance conductor or equivalent area of parallel conductors.
- 250.66(A): sole connection to rod, pipe or plate electrodes need not exceed 6 AWG copper or 4 AWG aluminum. 250.66(B): sole connection to a concrete-encased electrode need not exceed 4 AWG copper. 250.66(C): sole connection to a ground ring need not exceed the ring conductor size.
- 250.64(C) requires the GEC to be continuous, with splices permitted only by irreversible compression connectors, exothermic welding or connection to busbars.
- 250.64(A) restricts aluminum and copper-clad aluminum GECs from direct contact with masonry or earth and requires outdoor terminations at least 450 mm (18 in) above earth.
Step-by-Step Example Walkthrough
" A commercial service uses two parallel sets of 350 kcmil copper per phase. "
- 1. Equivalent area of the largest ungrounded conductor: 2 x 350 = 700 kcmil copper.
- 2. Table 250.66 row: over 600 through 1100 kcmil copper.
- 3. Minimum GEC from that row: 2/0 copper or 4/0 aluminum.