GEC Sizing (NEC 250.66)

Look up the minimum copper or aluminum grounding electrode conductor size from the largest service-entrance conductor using NEC 2023 Table 250.66, with the 250.66(A) to (C) electrode-specific limits.

Trades & Construction
Standard: NEC 2023 Table 250.66

Service Configuration

Choose the row by the largest ungrounded service-entrance conductor (or the equivalent area of parallel sets). The material selector sets the material of the grounding electrode conductor itself.

250.66(A)
Rod, Pipe or Plate
6 AWG Cu / 4 AWG Al
Max required for the sole connection
250.66(B)
Concrete-Encased
4 AWG Cu
Max required for the sole connection
250.66(C)
Ground Ring
Ring Size
Not required larger than the ring conductor

A metal underground water pipe electrode has no reduced size in 250.66, so the full Table 250.66 size applies to a GEC terminating on it.

NEC Table 250.66 — Full Lookup (Copper GEC)
Cu 2 AWG or smaller · Al 1/0 or smaller8 AWG
Cu 1 AWG or 1/0 · Al 2/0 or 3/06 AWG
Cu 2/0 or 3/0 · Al 4/0 or 250 kcmil4 AWG
Cu Over 3/0 to 350 kcmil · Al Over 250 to 500 kcmil2 AWG
Cu Over 350 to 600 kcmil · Al Over 500 to 900 kcmil1/0
Cu Over 600 to 1100 kcmil · Al Over 900 to 1750 kcmil2/0
Cu Over 1100 kcmil · Al Over 1750 kcmil3/0
Minimum GEC Size
4 AWG
Copper GEC — NEC Table 250.66
Calculated result for Service Conductors:

Service Conductors

Cu 2/0 or 3/0
Aluminum equivalent: 4/0 or 250 kcmil
Calculated result for Copper GEC:

Copper GEC

4 AWG
Per table
Calculated result for Aluminum GEC:

Aluminum GEC

2 AWG
Per table
Email LinkText/SMSWhatsApp

Worked Example: Service With 3/0 Copper Conductors

Calculator default row, NEC 2023 Table 250.66

Design Scenario

A dwelling service uses 3/0 AWG copper service-entrance conductors. The grounding electrode system includes a metal underground water pipe, a concrete-encased electrode and a ground rod.

Design Parameters
Largest service conductor3/0 AWG Cu
Table 250.66 row2/0 or 3/0 Cu (4/0 or 250 kcmil Al)
GEC materialCopper
Mathematical Solution
1Full-size GEC from Table 250.66

Applies to the GEC run to the water pipe electrode.

Row 2/0 or 3/0 Cu -> 4 AWG Cu (2 AWG Al)
2Concrete-encased electrode, 250.66(B)

Same as the table value in this case.

Not required larger than 4 AWG Cu
3Rod electrode bonding jumper, 250.66(A)

Where the conductor is the sole connection to the rod.

Not required larger than 6 AWG Cu
Engineering Conclusion: A 4 AWG copper GEC to the water pipe satisfies Table 250.66 for this service. The jumper whose only purpose is to connect the ground rod may be 6 AWG copper. Confirm installation and protection requirements in 250.64 and any local amendments.

Quick Answer

Use the largest ungrounded service-entrance conductor to find the row in NEC Table 250.66. A 2/0 or 3/0 copper service needs at least a 4 AWG copper or 2 AWG aluminum GEC. A conductor that is the sole connection to a ground rod need not exceed 6 AWG copper.

NEC 2023 Table 250.66 Summary

Largest service conductor, Cu Largest service conductor, Al or CCA Copper GEC Al or CCA GEC
2 AWG or smaller1/0 or smaller8 AWG6 AWG
1 or 1/02/0 or 3/06 AWG4 AWG
2/0 or 3/04/0 or 250 kcmil4 AWG2 AWG
Over 3/0 through 350 kcmilOver 250 through 500 kcmil2 AWG1/0
Over 350 through 600 kcmilOver 500 through 900 kcmil1/03/0
Over 600 through 1100 kcmilOver 900 through 1750 kcmil2/04/0
Over 1100 kcmilOver 1750 kcmil3/0250 kcmil

Summary for planning. Refer to the adopted edition of the NEC and its table notes for parallel conductors and other conditions.

Grounding Electrode Conductor vs. Equipment Grounding

This calculator determines the size of the Grounding Electrode Conductor (GEC) per NEC Table 250.66, which establishes the connection between the electrical service grounding system and earth electrodes (such as ground rods, concrete-encased Ufer electrodes, ground rings, or metal underground water pipes). GEC sizing is governed exclusively by the circular mil area of the largest ungrounded service-entrance conductors, not by the service overcurrent device rating.

In contrast, Equipment Grounding Conductors (EGC) are sized under NEC Table 250.122 based on the ampere rating of the upstream circuit breaker or fuse protecting the circuit. To evaluate circuit impedance and fault clearing characteristics along downstream branch runs, use our Ground Fault Loop Impedance Calculator.

Frequently Asked Questions

How do I size a grounding electrode conductor?

Find the largest ungrounded service-entrance conductor (or the equivalent area of parallel sets) in the left columns of NEC Table 250.66, then read the minimum GEC size for copper or aluminum in the same row. For a 3/0 copper service, the minimum copper GEC is 4 AWG.

When can the GEC be smaller than Table 250.66?

Under 250.66(A), the portion that is the sole connection to rod, pipe or plate electrodes is not required to be larger than 6 AWG copper or 4 AWG aluminum. Under 250.66(B), the sole connection to a concrete-encased electrode is not required to be larger than 4 AWG copper. Under 250.66(C), the sole connection to a ground ring is not required to be larger than the ring conductor.

What size GEC is needed for a metal water pipe electrode?

No reduced size applies to a metal underground water pipe electrode, so the conductor is sized from the full Table 250.66 row. NEC 250.53(D)(2) also requires the water pipe electrode to be supplemented by an additional electrode.

Can one GEC serve several electrodes?

Yes. A single GEC sized from Table 250.66 can run to any convenient electrode, with bonding jumpers interconnecting the electrodes to form the grounding electrode system. Under 250.53(C) those bonding jumpers are sized per 250.66, so a jumper whose only purpose is to connect a rod may use the 250.66(A) limit.

What restrictions apply to aluminum GECs?

NEC 250.64(A) does not permit bare, covered or insulated aluminum or copper-clad aluminum GECs in direct contact with masonry or earth or where subject to corrosive conditions. Outdoors, aluminum GEC terminations must be at least 450 mm (18 in) above the earth.

Is this the same as the equipment grounding conductor size?

No. Equipment grounding conductors for circuits are sized from the overcurrent device rating using Table 250.122. Table 250.66 applies to grounding electrode conductors and to some bonding jumpers that reference it.

Related Calculations

Calculation Provenance & Validation Record

Method

Direct lookup in NEC Table 250.66: the largest service-entrance conductor row gives the minimum copper or aluminum grounding electrode conductor, with 250.66(A) to (C) electrode-specific limits shown.

Formula
GECmin=f250.66(ASE, Material)GEC_{min} = f_{250.66}(A_{SE},\ \text{Material})
Assumptions
  • AC service; Table 250.66 is entered with the largest ungrounded service-entrance conductor or the equivalent area for parallel sets.
  • The full Table 250.66 size applies unless the GEC is the sole connection to a rod, pipe or plate electrode, a concrete-encased electrode, or a ground ring (250.66(A) to (C)).
  • Installation rules for protection, splicing and routing (250.64) still apply and are not checked by the calculator.
  • Local amendments adopted by the authority having jurisdiction may modify these requirements.
References
  • NFPA 70, National Electrical Code (NEC 2023) Table 250.66 - grounding electrode conductor for alternating-current systems
  • NEC 2023 250.66(A), (B), (C) - connections to rod/pipe/plate, concrete-encased and ground-ring electrodes
  • NEC 2023 250.64 - grounding electrode conductor installation; 250.53(C) - bonding jumpers between electrodes
Last substantive review:
Automated test status: 2 golden test vectors passing (GEC-01, GEC-02)
Method, assumptions & governing standards
Standard Sourced

Calculation Methodology

Direct lookup in NEC Table 250.66: the largest service-entrance conductor row gives the minimum copper or aluminum grounding electrode conductor, with 250.66(A) to (C) electrode-specific limits shown.

Governing Standard 2023

Standard:NFPA 70 (NEC) Table 250.66

Statutory building, electrical, and mechanical codes vary by jurisdiction. Confirm local municipality amendments before installation.

Key Assumptions & Constraints

  • AC service; Table 250.66 is entered with the largest ungrounded service-entrance conductor or the equivalent area for parallel sets.
  • The full Table 250.66 size applies unless the GEC is the sole connection to a rod, pipe or plate electrode, a concrete-encased electrode, or a ground ring (250.66(A) to (C)).
  • Installation rules for protection, splicing and routing (250.64) still apply and are not checked by the calculator.
  • Local amendments adopted by the authority having jurisdiction may modify these requirements.
Regression Tests: 2 golden vectors
Last Verified:
Primary References: 3 documented
Field Trade Notice: For trade planning and engineering estimates. Final installations must conform to project blueprints, authority having jurisdiction (AHJ) code approvals, and site-specific inspections.