What is Physics of Line Resistance (NEC 210.19)?
Mathematical Foundation
Laws & Principles
- The 3% Branch Guideline: NEC Section 210.19(A) Informational Note 4 recommends a maximum voltage drop of 3% for branch circuits to provide reasonable efficiency of operation.
- The 5% Feeder Rule: The total system drop (feeder from service to main panel plus branch circuit to equipment) should not collectively exceed 5% overall.
- Linear Relationship: Distance increases line resistance linearly. If 100 feet of wire drops 2%, then 200 feet under the same load drops 4% (exceeding the recommended 3% design threshold). Upsizing conductor gauge reduces line resistance.
- Copper vs. Aluminum: Aluminum has higher electrical resistivity than copper. Over long distances, conductor sizing must account for aluminum's higher resistance (e.g., upsizing conductor gauge) to keep voltage drop within recommended thresholds.
Step-by-Step Example Walkthrough
" Wiring a 15-amp load on a 120V single-phase circuit using standard 12 AWG Copper wire, running 125 feet out to a detached shed. "
- 1. Identify K-Factor: Copper = 12.9.
- 2. Identify CM for 12 AWG: 6,530 Circular Mils.
- 3. Apply single-phase formula: (2 × 12.9 × 15 Amps × 125 feet run) / 6,530 CM.
- 4. Calculate Raw Drop: 48,375 / 6,530 = 7.4 Volts dropped along the wire.
- 5. Calculate Percentage: (7.4V Drop / 120V Source) × 100 = 6.1% Drop.