What is NEC 110.9, Transformer Impedance, & Breaker AIC?
Mathematical Foundation
Laws & Principles
- NEC 110.9 (Interrupting Rating): Every circuit breaker and fuse must possess an interrupting rating equal to or exceeding the maximum available fault current at its line terminals. Installing an under-rated overcurrent device can lead to contact welding, severe enclosure rupture, and sustained arc energy release.
- The Impedance Inverse Law: A transformer with 2% impedance allows 50× FLA to flow during a bolted fault. A transformer with 5% impedance limits fault current to 20× FLA. Lower-impedance units yield tighter voltage regulation under load but increase prospective fault current and required equipment AIC ratings.
- NEC 110.24 (Available Fault Current Labeling): Service equipment in other than dwelling units must be field-marked with maximum available fault current and calculation date, updated whenever system modifications alter available current.
- Motor Contribution: Induction motors act as transient induction generators during the initial cycles of a fault, backfeeding prospective fault current into the short circuit. In industrial facilities with heavy rotating equipment, motor contribution can add significant symmetrical current above transformer-only calculations.
Step-by-Step Example Walkthrough
" A commercial facility is fed by a 75 kVA, 208V, 3-phase transformer with a nameplate impedance of 2.5%Z. The electrician determines minimum AIC-rated breakers for the main panelboard. "
- 1. Calculate Full Load Amps: FLA = (75 × 1000) ÷ (208 × 1.732) = 75,000 ÷ 360.3 = 208.2 Amps.
- 2. Calculate Impedance Multiplier: 100 ÷ 2.5 = 40×.
- 3. Calculate Available Fault Current: SCA = 208.2 × 40 = 8,328 Amps at transformer terminals.
- 4. Select Minimum AIC: The standard commercial AIC tier equal to or exceeding 8,328A is 10 kAIC (10,000 AIC).